Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC Service Port 102 access control

CVSS Meta Temp Score
CVSS is a standardized scoring system to determine possibilities of attacks. The Temp Score considers temporal factors like disclosure, exploit and countermeasures. The unique Meta Score calculates the average score of different sources to provide a normalized scoring system.
Current Exploit Price (≈)
Our analysts are monitoring exploit markets and are in contact with vulnerability brokers. The range indicates the observed or calculated exploit price to be seen on exploit markets. A good indicator to understand the monetary effort required for and the popularity of an attack.
CTI Interest Score
Our Cyber Threat Intelligence team is monitoring different web sites, mailing lists, exploit markets and social media networks. The CTI Interest Score identifies the interest of attackers and the security community for this specific vulnerability in real-time. A high score indicates an elevated risk to be targeted for this vulnerability.
7.3$5k-$25k0.00

Summaryinfo

A vulnerability marked as critical has been reported in Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC, SIMATIC ET 200SP Open Controller CPU 1515SP PC2, SIMATIC S7-1200 CPU, SIMATIC S7-1500 CPU, SIMATIC S7-1500 Software Controller and SIMATIC S7-PLCSIM Advanced. This affects an unknown function of the component Service Port 102. Performing a manipulation results in access control. This vulnerability was named CVE-2019-10943. The attack may be initiated remotely. There is no available exploit. It is suggested to use restrictive firewalling.

Detailsinfo

A vulnerability was found in Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC, SIMATIC ET 200SP Open Controller CPU 1515SP PC2, SIMATIC S7-1200 CPU, SIMATIC S7-1500 CPU, SIMATIC S7-1500 Software Controller and SIMATIC S7-PLCSIM Advanced (SCADA Software). It has been classified as critical. This affects an unknown code of the component Service Port 102. The manipulation with an unknown input leads to a access control vulnerability. CWE is classifying the issue as CWE-284. The product does not restrict or incorrectly restricts access to a resource from an unauthorized actor. This is going to have an impact on confidentiality, integrity, and availability. The summary by CVE is:

A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (All versions), SIMATIC S7-1200 CPU family (All versions >= V4.0), SIMATIC S7-1500 CPU family (All versions), SIMATIC S7-1500 Software Controller (All versions), SIMATIC S7-PLCSIM Advanced (All versions). An attacker with network access to port 102/tcp could potentially modify the user program on the PLC in a way that the running code is different from the source code which is stored on the device. An attacker must have network access to affected devices and must be able to perform changes to the user program. The vulnerability could impact the perceived integrity of the user program stored on the CPU. An engineer that tries to obtain the code of the user program running on the device, can receive different source code that is not actually running on the device. No public exploitation of the vulnerability was known at the time of advisory publication.

The weakness was presented 08/13/2019. This vulnerability is uniquely identified as CVE-2019-10943 since 04/08/2019. It is possible to initiate the attack remotely. No form of authentication is needed for exploitation. The technical details are unknown and an exploit is not publicly available. The pricing for an exploit might be around USD $5k-$25k at the moment (estimation calculated on 11/25/2023). The attack technique deployed by this issue is T1068 according to MITRE ATT&CK.

It is possible to mitigate the weakness by firewalling tcp/102.

See VDB-139981 for similar entry. Be aware that VulDB is the high quality source for vulnerability data.

Productinfo

Type

Vendor

Name

License

Website

CPE 2.3info

CPE 2.2info

CVSSv4info

VulDB Vector: 🔍
VulDB Reliability: 🔍

CVSSv3info

VulDB Meta Base Score: 7.4
VulDB Meta Temp Score: 7.3

VulDB Base Score: 7.3
VulDB Temp Score: 7.1
VulDB Vector: 🔍
VulDB Reliability: 🔍

NVD Base Score: 7.5
NVD Vector: 🔍

CVSSv2info

AVACAuCIA
💳💳💳💳💳💳
💳💳💳💳💳💳
💳💳💳💳💳💳
VectorComplexityAuthenticationConfidentialityIntegrityAvailability
UnlockUnlockUnlockUnlockUnlockUnlock
UnlockUnlockUnlockUnlockUnlockUnlock
UnlockUnlockUnlockUnlockUnlockUnlock

VulDB Base Score: 🔍
VulDB Temp Score: 🔍
VulDB Reliability: 🔍

NVD Base Score: 🔍

Exploitinginfo

Class: Access control
CWE: CWE-284 / CWE-266
CAPEC: 🔍
ATT&CK: 🔍

Physical: No
Local: No
Remote: Yes

Availability: 🔍
Status: Not defined

EPSS Score: 🔍
EPSS Percentile: 🔍

Price Prediction: 🔍
Current Price Estimation: 🔍

0-DayUnlockUnlockUnlockUnlock
TodayUnlockUnlockUnlockUnlock

Threat Intelligenceinfo

Interest: 🔍
Active Actors: 🔍
Active APT Groups: 🔍

Countermeasuresinfo

Recommended: Firewall
Status: 🔍

0-Day Time: 🔍

Firewalling: 🔍

Timelineinfo

04/08/2019 🔍
08/13/2019 +127 days 🔍
08/15/2019 +2 days 🔍
11/25/2023 +1563 days 🔍

Sourcesinfo

Vendor: siemens.com

Advisory: ssa-232418
Status: Not defined

CVE: CVE-2019-10943 (🔍)
GCVE (CVE): GCVE-0-2019-10943
GCVE (VulDB): GCVE-100-139983
See also: 🔍

Entryinfo

Created: 08/15/2019 06:59
Updated: 11/25/2023 07:42
Changes: 08/15/2019 06:59 (38), 07/27/2020 16:33 (18), 11/25/2023 07:42 (5)
Complete: 🔍
Cache ID: 216::103

Be aware that VulDB is the high quality source for vulnerability data.

Discussion

No comments yet. Languages: en.

Please log in to comment.

Do you know our Splunk app?

Download it now for free!